L&T DU400N MCCB 400A (320-400A) 3 Pole 50kA Thermal Magnetic | CM98402OORO
L&T DU400N MCCB 400A (320-400A) 3 Pole 50kA Thermal Magnetic | CM98402OORO Original price was: ₹26,900.00.Current price is: ₹16,947.00.
+ GST ₹3050.46
Back to products
Polycab FR PVC 90 Mtr. Wire
Polycab FR PVC 90 Mtr. Wire WhatsApp for today's price

L&T DU400N MCCB 400A (320-400A) 4 Pole 50kA Thermal Magnetic | CM98404OORO

₹24,532.20 Incl. of Taxes -37%Original price was: ₹33000.00.Current price is: ₹20790.00.+ GST ₹3,742.20 (18%)

+ GST (18%): ₹3742.20
Total payable: ₹24532.20

L&T / Lauritz Knudsen DU400N MCCB, catalog no. CM98404OORO
400A (320-400A), 4 Pole, 50kA @ 690V AC breaking capacity (Ics = 50% of Icu)
Adjustable thermal 0.8-1.0 x In, fixed magnetic 9 x In
GST invoice on every order | Same-day dispatch in Bengaluru for orders before 4 PM
Bulk and project rates on WhatsApp: +91 78160 62494

SKU: CM98404OORO Categories: , Tag:
Description

Looking for the L&T DU400N MCCB 400A 4 Pole? This is the genuine Lauritz Knudsen (formerly L&T Switchgear) DU series moulded case circuit breaker, catalog number CM98404OORO, made for feeder, incomer and sub-distribution protection in commercial buildings, industries and OEM panels. We stock it at our Chamrajpet shop in Bengaluru with a GST invoice on every order, same-day dispatch for orders placed before 4 PM (Monday to Saturday), and delivery across all of Bengaluru including outskirts. Free store pickup is available. For project and bulk rates, WhatsApp us on +91 78160 62494.

Breaking capacity is 50 kA at 415V AC, with Ics = 50% of Icu. The DU range gives you an adjustable thermal (overload) setting from 0.8 to 1.0 times In – this unit covers 400A (320-400A) – with a fixed magnetic short-circuit trip at 9 times the rated current (3600A here). That adjustability lets you trim the overload trip to the actual load and cable size during commissioning.

Spreader terminals are not included with this catalog number – if your panel needs them for cable termination (185 mm mm2 lugs), add the matching DU400N 4 pole spreader link set and, for panel-door operation, the direct or extended rotary handle from the Frequently Bought Together section below. One set covers one MCCB. Phase barriers are supplied with the unit.

Practical panel-builder details: no load-line bias, so supply and load can connect to either side; clear ON / TRIP / OFF indication; suitable for isolation; conforms to IS/IEC 60947-2, IEC 60947-2 and EN 60947-2.

Note on branding: L&T Switchgear is now Lauritz Knudsen Electrical & Automation (renamed in May 2024). Depending on stock, the unit may carry either the L&T or Lauritz Knudsen name. The catalog number, specifications and quality are identical.

📋 Technical Specifications

ParameterValue
BrandL&T / Lauritz Knudsen
Part Number / SKUCM98404OORO
CategoryMCCB (Moulded Case Circuit Breaker)
SeriesDU400N
Current Rating (In)400 A
Poles4 Pole
Breaking Capacity (Icu)50 kA @ 415V AC (Icu @ 415V AC)
Service Breaking Capacity (Ics)50% of Icu
Release TypeThermal-Magnetic (adjustable thermal, fixed magnetic)
Thermal (Overload) SettingAdjustable 0.8 – 1.0 x In (set 400A (320-400A))
Magnetic (Short Circuit) SettingFixed, 9 x In (3600 A for this 400A unit)
Rated Operational Voltage (Ue)690V AC, 50/60 Hz
Rated Insulation Voltage (Ui)800 V
Impulse Withstand Voltage (Uimp)8 kV
Utilization CategoryA
StandardIS/IEC 60947-2, IEC 60947-2, EN 60947-2
Terminal Capacity185 mm² cable with lug (link ≤32 mm)
Mechanical / Electrical Life10,000 / 4,000 operations
Dimensions (W x D x H)184 x 110.5 x 205 mm
Weight5 kg
IP Rating / IsolationIP40 (front), suitable for isolation

⚡ Key Features

  • Genuine L&T / Lauritz Knudsen DU400N MCCB – catalog no. CM98404OORO
  • 400A, 4 Pole, 50 kA breaking capacity at 690V AC (Ics = 50% of Icu)
  • Adjustable thermal release 0.8 – 1.0 x In; fixed magnetic trip at 9 x In
  • Phase barriers included; spreader terminals and rotary handles available separately below
  • No load-line bias – connect supply and load on either side
  • Clear ON / TRIP / OFF indication; suitable for isolation
  • GST invoice on every order; same-day dispatch in Bengaluru for orders before 4 PM

📄 Official Catalogue / Datasheet

Download the official L&T / Lauritz Knudsen DU/DY MCCB catalogue (covers DU400N technical data, trip curves, accessories and dimensions): DU/DY MCCB Catalogue (PDF, official)

❓ Frequently Asked Questions

Where can I use a 50 kA MCCB like the DU400N?

Use it where the prospective short-circuit level at the installation point is 50 kA or less – typically incomers and feeders in commercial and industrial distribution boards. Your panel designer or electrician works this out from the upstream transformer rating. If you need a higher fault level, the DU range goes up to 50 kA (DU400N) and the dsine DN range covers 25-100 kA – we stock both.

Can I adjust the trip settings on this MCCB?

Yes, partly – the DU400N has an adjustable thermal (overload) dial from 0.8 to 1.0 times In, so this 400A unit can be set anywhere in the 400A (320-400A) range. The magnetic short-circuit trip is fixed at 9 times the rated current (3600A on this unit). If you need finer electronic settings, look at the DN range with MTX microprocessor releases.

Are spreader terminals included with this MCCB?

No – CM98404OORO is the without-spreader variant, which keeps the price lower. If your panel needs spreader terminals for 4 pole cable termination, add the matching DU400N 4 pole spreader link set from the Frequently Bought Together section below – one set covers one MCCB.

How fast can you deliver in Bengaluru?

Orders placed before 4 PM, Monday to Saturday, are dispatched the same day. We deliver across all of Bengaluru including outskirts like Sarjapur, Anekal and the airport side. Delivery charges are confirmed with you before dispatch. You can also pick up free from our Chamrajpet shop.

Do I get a GST invoice and what are the payment options?

Every order comes with a GST invoice suitable for ITC claims and project billing. Payment is prepaid through PhonePe – UPI, cards and netbanking are all accepted. For bulk quantities and project rates, WhatsApp us on +91 78160 62494.

Additional information
BrandL&T
SeriesDU400N
Ampere400A
Poles4 Pole
Breaking Capacity50 kA
Trip UnitThermal Magnetic
Voltage Rating690V AC