L&T DY125U MCCB 100A 2 Pole 240V 25kA Thermal Magnetic | EM90812OOKO
₹1,903.10 Incl. of Taxes₹2,560.00 -37%Original price was: ₹2560.00.₹1,612.80Current price is: ₹1612.80.+ GST ₹290.30 (18%)
Total payable: ₹1903.10
L&T / Lauritz Knudsen DY125U MCCB, catalog no. EM90812OOKO
100A, 2 Pole, 240V AC, 25kA breaking capacity (Icu = Ics)
Fixed thermal-magnetic release – spreader terminals not included
GST invoice on every order | Same-day dispatch in Bengaluru for orders before 4 PM
Bulk and project rates on WhatsApp: +91 78160 62494
Looking for the L&T DY125U MCCB 100A 2 Pole? This is the genuine Lauritz Knudsen (formerly L&T Switchgear) DY series moulded case circuit breaker, catalog number EM90812OOKO, made for feeder and sub-distribution protection in shops, small industries, commercial buildings and OEM panels. We stock it at our Chamrajpet shop in Bengaluru with a GST invoice on every order, same-day dispatch for orders placed before 4 PM (Monday to Saturday), and delivery across all of Bengaluru including outskirts. Free store pickup is available. For project and bulk rates, WhatsApp us on +91 78160 62494.
The DY125U 2 Pole is built in the 3 pole frame size (75 mm width), so it matches the full DY125U accessory range. This catalog number EM90812OOKO is the variant spreader terminals not included. Phase barriers are supplied with the unit. The fixed thermal-magnetic release needs no settings or commissioning: overload protection is thermal and short-circuit protection trips magnetically at 10 times the rated current.
Breaking capacity is 25 kA at 240V AC (Ics = 100% of Icu) – the 2 pole DY125U is rated for 240V AC systems, with 10 kA at 250V DC when both poles are wired in series. If your installation is a 415V three-phase board, use the 3 pole or 4 pole DY125U instead, and where the fault level exceeds these values, look at the DU range (18-50 kA) or the dsine DN range – we stock those too.
Practical panel-builder details: no load-line bias, so supply and load can connect to either side; clear ON / TRIP / OFF indication; suitable for isolation; conforms to IS/IEC 60947-2, IEC 60947-2 and EN 60947-2. The whole DY125U family covers 16A to 125A in 2, 3 and 4 pole versions.
Note on branding: L&T Switchgear is now Lauritz Knudsen Electrical & Automation (renamed in May 2024). Depending on stock, the unit may carry either the L&T or Lauritz Knudsen name. The catalog number, specifications and quality are identical.
📋 Technical Specifications
| Parameter | Value |
|---|---|
| Brand | L&T / Lauritz Knudsen |
| Part Number / SKU | EM90812OOKO |
| Category | MCCB (Moulded Case Circuit Breaker) |
| Series | DY125U |
| Current Rating (In) | 100 A |
| Poles | 2 Pole (in 3 Pole frame size) |
| Breaking Capacity (Icu) | 25 kA (Icu = Ics) (@ 240V AC; 10 kA @ 250V DC (2P in series)) |
| Service Breaking Capacity (Ics) | 100% of Icu |
| Release Type | Thermal-Magnetic (fixed settings) |
| Thermal (Overload) Setting | Fixed |
| Magnetic (Short Circuit) Setting | Fixed, 10 x In (1000 A for this 100A unit) |
| Rated Operational Voltage (Ue) | 240V AC, 50/60 Hz |
| Rated Insulation Voltage (Ui) | 800 V |
| Impulse Withstand Voltage (Uimp) | 8 kV |
| Utilization Category | A |
| Standard | IS/IEC 60947-2, IEC 60947-2, EN 60947-2 |
| Terminal Capacity | 50 mm² cable with lug (link ≤17 mm); spreader terminals available separately – see Frequently Bought Together |
| Mechanical / Electrical Life | 30,000 / 8,000 operations |
| Dimensions (W x D x H) | 75 x 60 x 130 mm |
| Weight | 0.60 kg |
| IP Rating / Isolation | IP40 (front), suitable for isolation |
⚡ Key Features
- Genuine L&T / Lauritz Knudsen DY125U economy-range MCCB – catalog no. EM90812OOKO
- 100A, 2 Pole (3 pole frame size), 240V AC, 25 kA breaking capacity (Icu = Ics)
- Fixed thermal-magnetic release – no settings needed, works out of the box
- Phase barriers included; spreader terminals available separately below
- No load-line bias – connect supply and load on either side
- Clear ON / TRIP / OFF indication; suitable for isolation
- GST invoice on every order; same-day dispatch in Bengaluru for orders before 4 PM
📄 Official Catalogue / Datasheet
Download the official L&T / Lauritz Knudsen DU/DY MCCB catalogue (covers DY125U technical data, trip curves, accessories and dimensions): DU/DY MCCB Catalogue (PDF, official)
❓ Frequently Asked Questions
Where can I use a 25 kA 2 pole MCCB like the DY125U?
The 2 pole DY125U is rated 25 kA at 240V AC, so it suits 240V single-phase feeders and distribution boards where the prospective fault level is 25 kA or less. For 415V three-phase boards, pick the 3 pole or 4 pole version. Your panel designer or electrician confirms the fault level from the upstream transformer rating.
Can I adjust the trip settings on this MCCB?
No – the DY125U has a fixed thermal-magnetic release. Overload protection is thermal and short-circuit protection trips magnetically at 10 times the rated current (1000A on this 100A unit). That makes it simple and reliable with nothing to commission. If you need adjustable settings, look at the DU range or the dsine DN range with MTX microprocessor releases.
Are spreader terminals included with this MCCB?
No – EM90812OOKO is the without-spreader variant, which keeps the price lower. If your panel needs spreader terminals for 2 Pole cable termination, add the matching DY125U 2 Pole spreader link set from the Frequently Bought Together section below – one set covers one MCCB.
How fast can you deliver in Bengaluru?
Orders placed before 4 PM, Monday to Saturday, are dispatched the same day. We deliver across all of Bengaluru including outskirts like Sarjapur, Anekal and the airport side. Delivery charges are confirmed with you before dispatch. You can also pick up free from our Chamrajpet shop.
Do I get a GST invoice and what are the payment options?
Every order comes with a GST invoice suitable for ITC claims and project billing. Payment is prepaid through PhonePe – UPI, cards and netbanking are all accepted. For bulk quantities and project rates, WhatsApp us on +91 78160 62494.
| Brand | L&T |
|---|---|
| Series | DY125U |
| Ampere | 100A |
| Poles | 2 Pole |
| Breaking Capacity | 25 kA |
| Trip Unit | Thermal Magnetic |
| Voltage Rating | 240V AC |
Frequently Bought Together
L&T Rotary Handle DY125U Direct | EM90969OOOO
In stock
+ GST ₹209.79
L&T Rotary Handle DY125U Extended | EM90970OOOO
In stock
+ GST ₹301.64
L&T Spreader Link DY125U 2 Pole | CM97785OOO2
In stock
+ GST ₹45.36
Related products
L&T DY125U MCCB 125A 4 Pole 415V 10kA Thermal Magnetic | EM90984OOLO
In stock
+ GST ₹692.87
L&T DY125U MCCB 80A 2 Pole 240V 25kA Thermal Magnetic | EM90812OOJO
In stock
+ GST ₹290.30
L&T DY125U MCCB 80A 3 Pole 415V 10kA Thermal Magnetic | EM90813OOJO
In stock
+ GST ₹341.33
L&T DY125U MCCB 80A 3 Pole 415V 10kA Thermal Magnetic | EM90983OOJO
In stock
+ GST ₹384.43
L&T DY125U MCCB 80A 4 Pole 415V 10kA Thermal Magnetic | EM90814OOJO
In stock
+ GST ₹459.27
L&T DY125U MCCB 80A 4 Pole 415V 10kA Thermal Magnetic | EM90984OOJO
In stock
+ GST ₹530.71
L&T DY250U1 MCCB 200-250A 4 Pole 415V 10kA Thermal Magnetic | CM98196OOPO
In stock
+ GST ₹2029.86
L&T Spreader Link DY250U1 4 Pole | CM92007OOOO
In stock
+ GST ₹392.36

Legrand